Sign In | Join Free | My portofva.com |
|
Brand Name : GENY
Model Number : SZ03A-K6
Certification : ISO, CE
Place of Origin : China
MOQ : 1
Price : negotiate rates
Payment Terms : T/T, L/C, D/P, T/T
Supply Ability : 2 sets/ 3 months
Delivery Time : 6~8weeks
Packaging Details : Plywood cases
Test Voltage Range : 30V – 480V
Test Current Range : 10mA – 120A
Phase Angle : 0º – 360º
Test Frequency : 45Hz – 65Hz
Voltage Supply : 220V ± 10%, 50/60Hz ± 2Hz
Relative Humidity : 45% -- 75%
SZ03A-K6 | |
Test Voltage | |
Range | 30V – 480V |
Error | ±0.05% (30V – 480V) ±0.1% (5V – 50V) |
Display range | 5.000000V – 480.0000V |
Test Current | |
Range | 10mA – 120A |
Error | ±0.05% (0.2A – 120A) ±0.1% (10mA – 0.2A) |
Display range | 1.000000mA-120.0000A |
Power measure error | |
Active power | ±0.05% (0.2A – 120A) |
Reactive power | ±0.1% (0.2A – 120A) |
Apparent power | ±0.1% (0.2A – 120A) |
Energy measure error | |
Active energy | -- |
Reactive energy | -- |
Apparent energy | -- |
Phase angle | |
Range | 0º – 360º |
Error | ±0.05º |
Display range | 0.000001º -- 359.9999º |
Frequency | |
Range | 45Hz – 65Hz |
Display range | 45.0000 – 65.0000 |
Pulse output | |
High frequency output(CH) | 1×109 (0.2A – 1A) 1×108 (1A – 10A) 1×107 (10A – 120A) |
Low frequency output(CL) | 2×10-5×CH |
Pulse ratio | 1:1 |
Output level | 5V |
Pulse input | |
Input level | -- |
Input frequency | -- |
Other | |
Voltage Supply | 220V ± 10%, 50/60Hz ± 2Hz |
Ambient temperature | 10°C -- 30°C |
Influence of external fields | ≤ 0.05 % / mT |
Relative humidity | 45% -- 75% |
Dimensions (W×H×D) (mm) | 432×131×308 |
Weight (kg) | 15 |
This is wide current range Three Phase Reference Standard Meter, suit for Stationary Three Phase Energy Meter Test System.
1. High accuracy up to 0.05%
2. Testing type: 3 phase 4 wire, 3 phase 3 wire
3. Testing mode: active power, reactive power, cross connection reactive power
4. Measuring voltage, current, phase, frequency, power etc of each phase
5. Measuring phase angle of phase to phase, sum of active power, sum of reactive power etc
6. Test data can be managed by computer via Rs232 interface
![]() |
3ph Reference Standard Meter 10Ma – 120A Calibration Of Electrical Test Equipment Images |